300/500 V 90°C 60227 IEC 08 (HVSF)

Single-core Non-sheathed Cable With Flexible Conductor

Application

Use for general purpose

For installation in raceway and shall be protected water into raceway

Do not install in duct in ground or direct burial in ground

Construction

Conductor:Bunch stranded annealed copper

Insulation:Polyvinyl chloride(PVC). Black, Light Blue, Brown, Grey, Green/Yellow
or other colours

Reference Standard

TIS 11 Part 3-2553

Technical Characteristics

Maximum conductor temperature : 90°C

Rated voltage : 300/500 V

AC test voltage : 2,000 V

Conductor Thickness of insulation Overall diameter Insulation resistance at 70 °C (Min.) Current rating in free air Cable weight (Approx.)
Cross-sectional area No. of wires (Min.) Diameter (Approx.) Lower limit Upper limit
mm2   mm mm mm mm km A kg/km
0.5 0.21 0.92 0.6 2.1 2.5 0.013 3 9
0.75 0.21 1.13 0.6 2.2 2.7 0.012 6 12
1 0.21 1.31 0.6 2.4 2.8 0.010 10 15
1.5 0.26 1.58 0.7 2.8 3.4 0.009 16 22
2.5 0.26 2.04 0.8 3.4 4.1 0.009 25 35

 

 