300/500 V 70°C 60227 IEC 10

3 Cores - Light Polyvinyl Chloride Sheathed Cable

Application

Use for general purpose

For installation in raceway and shall be protected water into raceway

Laid on cable trays/Cable ladder

Do not install in duct in ground or direct burial in ground

Construction

Conductor:Solid or circular stranded annealed copper

Insulation:Polyvinyl chloride (PVC).Brown, Black, Grey

Inner covering:Polyvinyl chloride (PVC), Black colour

Outer sheath : Polyvinyl chloride (PVC), Black colour

Reference Standard

TIS 11 Part 4-2553

Technical Characteristics

Maximum conductor temperature : 70°C

Rated voltage : 300/500 V

AC test voltage : 2,000 V

No. of core Conductor Thickness of insulation Thickness of inner covering (Approx.) Thickness of outer sheath Overall diameter Insulation resistance at 70 °C (Min.) Current rating Laid on cable ladder Cable weight (Approx.)
Cross-sectional area No. of wires (Min.) Diameter (Approx.)
Lower limit Upper limit
  mm2   mm mm mm mm mm mm km A kg/km
3 1.5 1 1.36 0.7 0.4 1.2 8.0 10.5 0.011 16 140
3 1.5 7 1.53 0.7 0.4 1.2 8.2 11.0 0.010 16 150
3 2.5 1 1.75 0.8 0.4 1.2 9.2 12.0 0.010 22 190
3 2.5 7 1.98 0.8 0.4 1.2 9.4 12.5 0.009 22 210
3 4 1 2.21 0.8 0.4 1.2 10.0 13.0 0.0085 30 250
3 4 7 2.49 0.8 0.4 1.2 10.5 13.5 0.0077 30 270
3 6 1 2.70 0.8 0.4 1.4 11.5 14.5 0.0070 37 340
3 6 7 3.09 0.8 0.4 1.4 12.0 15.5 0.0065 37 370
3 10 1 3.50 1.0 0.6 1.4 14.0 17.5 0.0070 52 540
3 10 7 3.99 1.0 0.6 1.4 14.5 19.0 0.0065 52 590
3 16 7 5.01 1.0 0.8 1.4 16.5 21.5 0.0052 70 840
3 25 7 6.30 1.2 0.8 1.6 20.5 26.0 0.0050 88 1,270
3 35 7 7.55 1.2 1.0 1.6 22.0 29.0 0.0044 110 1,680

 

 

2017 © Caledonian All right reserved.
"Produce standard electrical cables. And timely service